Elkhart-brass 7095 EXM CAN Stow Module User Manual

Browse online or download User Manual for Equipment Elkhart-brass 7095 EXM CAN Stow Module. Elkhart Brass 7095 EXM CAN Stow Module User Manual

  • Download
  • Add to my manuals
  • Print
  • Page
    / 4
  • Table of contents
  • BOOKMARKS
  • Rated. / 5. Based on customer reviews
Page view 0
PHYSICAL: 1302 WEST BEARDSLEY AVE ELKHART, IN 46514 WWW.ELKHARTBRASS.COM © 2014 ELKHART BRASS MFG. CO., INC.
MAILING: P.O. BOX 1127 ELKHART, IN 46515 1-574-295-8330 1-800-346-0250 98533000 REV REL
EXM CAN Stow Module
Model: 7095
Troubleshooting Guide
This guide provides troubleshooting tips for the 7095 EXM CAN Stow Module. If the Stow Module still
does not work properly after checking the potential issues found in this guide, please contact Elkhart
Brass for further assistance.
CONFIGURATION ISSUES
The Stow Module only requires configuration if the monitor group number is NOT the same as that of
the Stow Module. Monitors and Stow Modules sold individually are configured to Group 1 by default,
and those should not need to be configured prior to installation. Those sold in packages or for multi-
monitor systems may have different group numbers. If you need to verify the Monitor Group number,
follow the steps under Operating Instructions step M. Write Diagnostic File* in an EXM monitor manual**.
If needed, the EXM CAN Stow Module’s group number can be changed, prior to installation, by following
the instructions below.
Ensure that proper Electrostatic Discharge (ESD)
precautions are taken and that the Stow Module is not
connected to a power supply.
Remove the cover of the Stow Module enclosure by
using a straight screwdriver to disengage the circuit
board header clips.
Find the Selection Switch “SW1” on the circuit board.
Using a straight screwdriver, carefully turn SW1 to the
desired Group Number minus one. (For example, if
you want to configure for a Group 3 Monitor, point the
SW1 arrow to 2). Standard setting is 0 for Group 1.
Carefully close the enclosure. Be sure the red seal is
not pinched or damaged when closing. Ensure both
clips click into place on either side of the enclosure.
The red seal should no longer be visible.
Install the Stow Module according to Installation
Instructions Step 1 EXM CAN Stow Module in an EXM
monitor manual**.
*Operating Instruction step letter may not match ‘M’. In this case, refer to the section title “Write Diagnostic File” for instructions.
**EXM monitor manual refers to the Sidewinder EXM, Cobra EXM, Scorpion EXM, etc.
Page view 0
1 2 3 4

Summary of Contents

Page 1 - EXM CAN Stow Module

PHYSICAL: 1302 WEST BEARDSLEY AVE • ELKHART, IN 46514 • WWW.ELKHARTBRASS.COM © 2014 ELKHART BRASS MFG. CO., INC. MAILING: P.O. BOX 1127 • ELKHART

Page 2

PHYSICAL: 1302 WEST BEARDSLEY AVE • ELKHART, IN 46514 • WWW.ELKHARTBRASS.COM © 2014 ELKHART BRASS MFG. CO., INC. MAILING: P.O. BOX 1127 • ELKHART

Page 3

PHYSICAL: 1302 WEST BEARDSLEY AVE • ELKHART, IN 46514 • WWW.ELKHARTBRASS.COM © 2014 ELKHART BRASS MFG. CO., INC. MAILING: P.O. BOX 1127 • ELKHART

Page 4

PHYSICAL: 1302 WEST BEARDSLEY AVE • ELKHART, IN 46514 • WWW.ELKHARTBRASS.COM © 2014 ELKHART BRASS MFG. CO., INC. MAILING: P.O. BOX 1127 • ELKHART

Comments to this Manuals

No comments